Prevention of legionella infections from toilet flushing cisterns

J Hosp Infect. 2024 Apr:146:37-43. doi: 10.1016/j.jhin.2023.12.016. Epub 2024 Jan 13.

Abstract

Introduction: Immunocompromised patients are at an increased risk of severe legionella infections. We present the results of an outbreak investigation initiated following a fatal case of hospital-acquired legionellosis linked to contaminated water from a toilet-flushing cistern. Additionally, we provide experimental data on the growth of Legionella spp. in flushing cisterns and propose a straightforward protocol for prevention.

Methods: We monitored the growth of Legionella spp. in the building's hot- and cold-water systems using quantitative bacterial culture on selective agar. Molecular typing of Legionella pneumophila isolates from the infected patient and the water system was conducted through core-genome multi-locus sequence typing (cgMLST).

Results: Legionella contamination in the hospital building's cold-water system was significantly higher than in the hot-water system and significantly higher in toilet flushing cistern's water compared with cold water from bathroom sinks and showers. Isolates from the patient and from the flushing cistern of the patient's bathroom were identical by cgMLST. In an experimental setting, daily toilet flushing for a period of 21 days resulted in a 67% reduction in the growth of Legionella spp. in the water of toilet flushing cisterns. Moreover, a one-time disinfection of cisterns with peracetic acid, followed by daily flushing, decreased legionella growth to less than 1% over a period of at least seven weeks in these setting.

Conclusions: One-time disinfection of highly contaminated cisterns with peracetic acid and daily toilet flushing as short-term measure can significantly reduce legionella contamination in flushing cisterns. These measures may aid in preventing legionella infection among immunocompromised patients.

Keywords: Hospital-acquired legionellosis; Immunocompromised patients; Legionella infection; Peracetic acid; Toilet; Toilet-flushing cistern.

MeSH terms

  • Bathroom Equipment*
  • Humans
  • Legionella pneumophila*
  • Legionella*
  • Legionellosis* / prevention & control
  • Multilocus Sequence Typing
  • Peracetic Acid
  • Water
  • Water Microbiology
  • Water Supply

Substances

  • Peracetic Acid
  • Water